Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM00906
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/13/2006 | ANY | ENGINEERING | REVIEW | Approved | |
| 02/13/2006 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 02/14/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The applicable code is the 2003 UPC with local amendments. 2. Provide a riser diagram for the water. Show how the new piping relates to the existing piping and show that the new connections do not overload the existing piping. 3. Revise the waste and vent riser diagram to provide traps for all fixtures. (Note that the existing washer drain is probably not shown correctly.) 4. Provide upper terminal cleanouts per Section 707.4, UPC 2003. 5. Provide vents for all of the fixtures. 6. SDR 35 PVC waste piping is not approved for use inside a building. |
| 02/14/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 02/14/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 03/17/2006 | AOLIVO1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 03/17/2006 | AOLIVO1 | WWM | REVIEW | Needs Review | |
| 03/17/2006 | AOLIVO1 | FIRE | REVIEW | Needs Review | |
| 03/17/2006 | AOLIVO1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |