Permit Number: T06CM00906
Parcel: 122132200

Address:
3962 E PIMA ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM00906
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/13/2006 ANY ENGINEERING REVIEW Approved
02/13/2006 TERRY STEVENS ZONING REVIEW Approved
02/14/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The applicable code is the 2003 UPC with local amendments.
2. Provide a riser diagram for the water. Show how the new piping relates to the existing piping and show that the new connections do not overload the existing piping.
3. Revise the waste and vent riser diagram to provide traps for all fixtures. (Note that the existing washer drain is probably not shown correctly.)
4. Provide upper terminal cleanouts per Section 707.4, UPC 2003.
5. Provide vents for all of the fixtures.
6. SDR 35 PVC waste piping is not approved for use inside a building.
02/14/2006 ROBERT SHERRY WATER REVIEW Approved
02/14/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
03/17/2006 AOLIVO1 BUILDING-COMMERCIAL REVIEW Needs Review
03/17/2006 AOLIVO1 WWM REVIEW Needs Review
03/17/2006 AOLIVO1 FIRE REVIEW Needs Review
03/17/2006 AOLIVO1 ELECTRICAL-COMMERCIAL REVIEW Needs Review