Review Date Reviewer's Name Type of Review Description Status Comments
02/10/2006 MBROWN3 FIRE REVIEW Approved
02/10/2006 ANY PLUMBING-COMMERCIAL REVIEW Active
02/10/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
02/10/2006 ANY WWM REVIEW Active
02/10/2006 HEATHER THRALL ZONING REVIEW Approved
02/10/2006 ANY MECHANICAL-COMMERCIAL REVIEW Active
02/10/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM00853 2/10/06

1. With the addition of the track lighting, demonstrate compliance with the 2003 IECC.
2. Please note that Show Window receptacles are to be counted as 200VA/LF, not per circuit. Reference NEC 220.3 (B) (7).
3. It appears that the final line of the SES load calculations did not print out.
02/10/2006 ANY WATER REVIEW Active
02/10/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved