| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/10/2006 | MBROWN3 | FIRE | REVIEW | Approved | |
| 02/10/2006 | ANY | PLUMBING-COMMERCIAL | REVIEW | Active | |
| 02/10/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/10/2006 | ANY | WWM | REVIEW | Active | |
| 02/10/2006 | HEATHER THRALL | ZONING | REVIEW | Approved | |
| 02/10/2006 | ANY | MECHANICAL-COMMERCIAL | REVIEW | Active | |
| 02/10/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM00853 2/10/06 1. With the addition of the track lighting, demonstrate compliance with the 2003 IECC. 2. Please note that Show Window receptacles are to be counted as 200VA/LF, not per circuit. Reference NEC 220.3 (B) (7). 3. It appears that the final line of the SES load calculations did not print out. |
| 02/10/2006 | ANY | WATER | REVIEW | Active | |
| 02/10/2006 | SUZANNE BOHNET | ENGINEERING | REVIEW | Approved |