Permit Number: T06CM00843
Parcel: 11016068B

Address:
6111 E GRANT RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM00843
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/10/2006 MBROWN3 FIRE REVIEW Approved
02/10/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
02/10/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) PROVIDE A BUILDING FLOOR PLAN CLARIFYING MOST RESTRICTIVE USE. AND SHOW ACCESSIBILTY PATH FROM PARKING LOT ALL THE WAY TO RESTROOM.
2) PROVIDE 20% COST OF CONSTRUCTION BREAKDOWN ON DRAWINGS JUSTIFYING BEING SPENT TOWARDS ACCESSIBLITY REQUIREMENTS PER ANSI 2003 A117.1 OR SHOW CLEAR FLOOR SPACE ENVELOPES IN UNISEX BATHROOM TO CLARIFY RESTROOM IS FULLY ACCESSIBLE.
3)NEED TO APPEAL BUILDING OFFICIAL FOR PRIVATE RESTROOMS THAT ARE NOT ACCESSIBLE.
4) CLARIFY WORK SURFACE IN KITCHEN MEETS ANSI A117.1 2003 SECTION 902.3.
02/10/2006 ROBERT SHERRY WATER REVIEW Approved
02/10/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
02/10/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Note on sheet A1.0 appears to indicate that the mechanical design for this project was done by a mechanical contractor and sealed by the architect. This is in violation of the regulatory provisions of the Arizona Board of Technical Registration: " A registrant shall not sign, stamp or seal any professional documents not prepared by the registrant or a bona fide employee".
1. The 2003 International Mechanical Code is the relevant code for this project, not the 1994 UMC.
2. Recirculation of ventilation air from toilet rooms is prohibited. Provide a sequence of operation for the restroom exhaust fans that demonstrates that no recirculation will occur. Reference Table 403.3 IMC 2003.
3. Provide information to verify that the existing roof is capable of supporting the additional dead load due to the installation of the roof top unit. Reference Section 302.1, IMC 2003.
02/13/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved
02/14/2006 PETER MCLAUGHLIN ZONING REVIEW Approved
03/07/2006 AOLIVO1 WWM REVIEW Needs Review