Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM00842
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/10/2006 | MBROWN3 | FIRE | REVIEW | Approved | |
| 02/10/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 02/10/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) PROVIDE A VALUATION FOR PROJECT. 2) CLARIFY RATING OF FIRE BARRIER FOR SEPERATION BETWEEN TENANTS AND OCCUPANCY NEXT DOOR TO TENANT SPACE. 3) PROVIDE TOTAL SQUARE FOOTAGE OF BUILDING. 4) WALL FINISH FOR RESTROOM FACILITY NEEDS TO BE SPECIFIED PER IBC 2003 SECTION 1210.2 |
| 02/10/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 02/10/2006 | CFOREMA1 | ENGINEERING | REVIEW | Approved | |
| 02/13/2006 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 02/23/2006 | RSHERRY1 | WWM | REVIEW | Passed | |
| 02/23/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T06CM00842 2/10/06 1. Provide a disconnect for the sign circuit. Reference NEC 600.6. 2. Provide voltage and phase on electrical panel. 3. Provide load calculations on panel schedule. 4. Load calculations on plans do not appear to apply to anything. If they are panel calculations, it is obvious that the 200A panel is overloaded with a 314 A load. If this is a service load calculation, it is questionable that a 2000A service would only carry 314A. |
| 03/06/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved |