02/10/2006 MBROWN3 FIRE REVIEW Approved
02/10/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
02/10/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) PROVIDE A VALUATION FOR PROJECT.
2) CLARIFY RATING OF FIRE BARRIER FOR SEPERATION BETWEEN TENANTS AND OCCUPANCY NEXT DOOR TO TENANT SPACE.
3) PROVIDE TOTAL SQUARE FOOTAGE OF BUILDING.
4) WALL FINISH FOR RESTROOM FACILITY NEEDS TO BE SPECIFIED PER IBC 2003 SECTION 1210.2
02/10/2006 ROBERT SHERRY WATER REVIEW Approved
02/10/2006 CFOREMA1 ENGINEERING REVIEW Approved
02/13/2006 DAVID RIVERA ZONING REVIEW Approved
02/23/2006 RSHERRY1 WWM REVIEW Passed
02/23/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T06CM00842 2/10/06

1. Provide a disconnect for the sign circuit. Reference NEC 600.6.
2. Provide voltage and phase on electrical panel.
3. Provide load calculations on panel schedule.
4. Load calculations on plans do not appear to apply to anything. If they are panel calculations, it is obvious that the 200A panel is overloaded with a 314 A load. If this is a service load calculation, it is questionable that a 2000A service would only carry 314A.
03/06/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved