Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T06CM00832
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/09/2006 | JWILLIA5 | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/09/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM00832 2/9/06 1. Demonstrate compliance with the Tucson Lighting Code, http://www.tucsonaz.gov/dsd/Codes___Ordinances/Tucson_Lighting_Code.pdf. 2. Clarify which lighting fixtures are to go on which circuits. 3. Show the grounding electrode system on line diagram. 4. Please note that TEP does not provide 480V, single phase service. Suggest to check with the Developer. |
| 02/15/2006 | JOSE ORTIZ | ENGINEERING | REVIEW | Approved | |
| 02/17/2006 | HEATHER THRALL | ZONING | REVIEW | Passed |