Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06CM00826
Parcel: 124041020

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM00826
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/23/2006 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Approved
02/23/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T06CM00826 2/23/06

1. 2003 IECC allows 1.7W/SF for Retail, not 2.1.
2. Tucson Lighting Code 4.13 requires the entire parcel to be considered in the computation of net acreage.
3. It is not clear from the plans that the exterior lighting fixture is FCO. Provide catalogue cut sheet.
02/27/2006 GERRY KOZIOL WWM REVIEW Completed