Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T06CM00826
Parcel: 124041020

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM00826
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/15/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved
02/15/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM00826 2/15/06

1. Provide a lighting fixture schedule for all new lighting.
2. Demonstrate compliance with the 2003 IECC for this occupancy.
3. For the purpose of feeder load calculations track lighting shall be counted at 75VA/LF. Reference NEC220.12 (B).
4. Account for continuous load on panel schedule load calculations.
5. Provide service load calculations.
6. Clarify that this is an existing panel, if such is the case.
7. Data on the existing water heater does not appear to be correct. With 6240 VA, it would operate at 52A. This could not happen on a 40A circuit.
8. Demonstrate compliance with the Tucson Lighting Code.
02/22/2006 MICHAEL ST. PAUL ZONING REVIEW Approved
02/23/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
02/23/2006 DROBEY1 BUILDING-COMMERCIAL REVIEW Needs Review
02/23/2006 DROBEY1 WWM REVIEW Needs Review
02/23/2006 MARTIN BROWN FIRE REVIEW Approved
02/23/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
02/23/2006 ROBERT SHERRY WATER REVIEW Approved