Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06CM00810
Parcel: 12206051C

Address:
4400 E GRANT RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM00810
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/23/2006 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Approved
02/23/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the ventilation calculations to include the common ventilation calculations per Section 403.3.2, IMC 2003.
02/23/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied t06cm00810 2/23/06

1. Account for track lighting demand on panel schedule. Reference NEC 220.12 (B).
2. Account for continuous loading 1.25% demand factor for track lighting.
3. Hair dryer station schedule calls for 8.3 MAX amps, (8.3) (120) = 996 VA. Ckts 33, 34, 35, & 36 call for 180VA. Please clarify.
02/23/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide reduced pressure backflow preventers on the hot and cold water supplies to the foot spa.
2. Provide an indirect waste recepter for the reduced pressure backflow preventers.
03/06/2006 GBONILL1 WWM REVIEW Needs Review