Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T06CM00810
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/23/2006 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Approved | |
02/23/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the ventilation calculations to include the common ventilation calculations per Section 403.3.2, IMC 2003. |
02/23/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | t06cm00810 2/23/06 1. Account for track lighting demand on panel schedule. Reference NEC 220.12 (B). 2. Account for continuous loading 1.25% demand factor for track lighting. 3. Hair dryer station schedule calls for 8.3 MAX amps, (8.3) (120) = 996 VA. Ckts 33, 34, 35, & 36 call for 180VA. Please clarify. |
02/23/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide reduced pressure backflow preventers on the hot and cold water supplies to the foot spa. 2. Provide an indirect waste recepter for the reduced pressure backflow preventers. |
03/06/2006 | GBONILL1 | WWM | REVIEW | Needs Review |