Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T06CM00810
Parcel: 12206051C

Address:
4400 E GRANT RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM00810
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/08/2006 MBROWN3 FIRE REVIEW Approved
02/08/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide water and waste riser diagrams.
2. Show how the foot spa is to be installed.
3. Show plumbing design on the plans.
02/08/2006 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied S1. PROVIDE CORRECTED CODE REVIEW CHECKLIST.
S2. ADDRESS ACCESSIBILTY, SHOW WHERE 20% OF PROJECT COST IS SPENT ON ACCESSIBILITY, PER IBC SEC 34, PROVIDE ESTIMATE ON DRAWING A0 AND DETAILS ON DRAWINGS.
S3. CLARIFY OCCUPANT LOAD ON DRAWINGS.
S4. PROVIDE 2ND ACCESSIBLE TOILET ROOM, BASED ON OCCUPANT LOAD OVER 15.
S5. CLARIFY CONNECTIONS TO STRUCTURE AT TOP OF WALLS, SHOW FASTENER TYPE, SIZE, SPACING/NUMBER.
02/08/2006 ROBERT SHERRY WATER REVIEW Approved
02/08/2006 MICHAEL ST. PAUL ZONING REVIEW Approved
02/08/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide a mechanical design, including ventilation calculations. Reference Sections 403.3 and 403.3.2, IMC 2003.
2. Substitute or equivalent plumbing fixtures are to be approved by the architect prior to installation, not the COT inspector.
3. All lettering shall be at least 1/8" and all caps.
02/08/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM00810 2/8/06

1. Provide an updated panel schedule.
2. Please note that according to NEC 334.10 (3), the "romex" shall be concealed behind a wall, floor, or ceiling with a 15-minute finish rating as identified in listings of fire-rated assemblies.
3. Note that romex is prohibited as an open run in dropped or suspended ceilings. Reference NEC 334.12 (A) (1).
4. Provide schedule for the new lighting fixture.
5. Demonstrate compliance with the 2003 IECC. Reference 101.2.2.4, 805.5.2.
02/08/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved
02/23/2006 DROBEY1 WWM REVIEW Needs Review