Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM00810
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/08/2006 | MBROWN3 | FIRE | REVIEW | Approved | |
02/08/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide water and waste riser diagrams. 2. Show how the foot spa is to be installed. 3. Show plumbing design on the plans. |
02/08/2006 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Denied | S1. PROVIDE CORRECTED CODE REVIEW CHECKLIST. S2. ADDRESS ACCESSIBILTY, SHOW WHERE 20% OF PROJECT COST IS SPENT ON ACCESSIBILITY, PER IBC SEC 34, PROVIDE ESTIMATE ON DRAWING A0 AND DETAILS ON DRAWINGS. S3. CLARIFY OCCUPANT LOAD ON DRAWINGS. S4. PROVIDE 2ND ACCESSIBLE TOILET ROOM, BASED ON OCCUPANT LOAD OVER 15. S5. CLARIFY CONNECTIONS TO STRUCTURE AT TOP OF WALLS, SHOW FASTENER TYPE, SIZE, SPACING/NUMBER. |
02/08/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
02/08/2006 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
02/08/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide a mechanical design, including ventilation calculations. Reference Sections 403.3 and 403.3.2, IMC 2003. 2. Substitute or equivalent plumbing fixtures are to be approved by the architect prior to installation, not the COT inspector. 3. All lettering shall be at least 1/8" and all caps. |
02/08/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM00810 2/8/06 1. Provide an updated panel schedule. 2. Please note that according to NEC 334.10 (3), the "romex" shall be concealed behind a wall, floor, or ceiling with a 15-minute finish rating as identified in listings of fire-rated assemblies. 3. Note that romex is prohibited as an open run in dropped or suspended ceilings. Reference NEC 334.12 (A) (1). 4. Provide schedule for the new lighting fixture. 5. Demonstrate compliance with the 2003 IECC. Reference 101.2.2.4, 805.5.2. |
02/08/2006 | SUZANNE BOHNET | ENGINEERING | REVIEW | Approved | |
02/23/2006 | DROBEY1 | WWM | REVIEW | Needs Review |