Permit Number: T06CM00764
Parcel: 140420150

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM00764
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/12/2006 MARTIN BROWN FIRE REVIEW Approved
07/13/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Appliances (e.g. coffee brewer, commercial ice maker, etc.) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps require backflow prevention. Reference Sections 602.3, 603.0, and Table 6-2, UPC 2003.
07/13/2006 ROBERT SHERRY WATER REVIEW Approved
07/24/2006 PETER MCLAUGHLIN ZONING REVIEW Approved
07/26/2006 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied 1) Provide roof diaphragm calc`s, or show where they can
be found in calc`s.
07/27/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.


1. Provide GFCI protection for Elevator Equipment room per NEC 620.85. This was done for one such receptacle in Room 251, but not the other.
2. Sheet E6.3 SB MSB1 size the EGC for Panel L1P.
3. Provide power for AC-15 and CU-15, as specified on Sheet M5.1, Mechanical Revision #4, 5/31/06.
4. Lumen calculations on Sheet E6.6 contain the following errors: Total Mean Lumens for Fixture D19 appears to be 23,760, not 11,880; Total Mean Lumens for Fixture D20 appears to be 6650, not 3325; Total Mean Lumens for entire property appears to be 693,610, not 678,405; Total Mean Lumens for unshielded component appears to be 54,310, not 39,105. The site still appears to be in compliance, but margins are slimmer such that it justifies the above corrections.
5. Electrical Plans Examiner has noticed that a Fire Pump and Jockey Pump have been called out on Sheet FP1.2. Please note that if this is the intent, such items shall be included in the Electrical design, and shall meet all requirements of NEC Article 695.
08/03/2006 GERRY KOZIOL WWM REVIEW Denied cannot drain /backwash pool into public sewer. needs manhole construction permit
08/16/2006 LOREN MAKUS ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/24/2006 JMORALE1 OUT TO CUSTOMER Completed
08/24/2006 SUE REEVES REJECT SHELF Completed