Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM00735
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/06/2006 | MBROWN3 | FIRE | REVIEW | Approved | |
| 02/06/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide information to show how the existing gas piping system is being affected by the addition of new gas loads. |
| 02/06/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 02/06/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide additional design information for the spray booth and its exhaust system to show that they comply to the requirements of Section 502.7, IMC 2003. 2. Provide information on the type of processes being conducted in the Flash/Drying room, the material quantities, and show how the operation complies to Section 502, IMC 2003. 3. The condensate from HX-1 may not terminate into the tailpiece of a sink. Reference Section 307.2.1, IMC 2003. 4. Clarify how F-1 is being installed and how the unit is being vented. Reference Section 106.3.1, IMC 2003. 5. Provide structural calculations and framing details to show that the installation of HX-1 will not overstress the roof. Reference Section 302.1, IMC 2003. 6. State the minimum R-value to be used for the HVAC duct insulation. Reference Section 803, IECC 2003. 7. Show how make up air is being supplied to the building. Reference Section 501.3, IMC 2003. |
| 03/27/2006 | AOLIVO1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 03/27/2006 | AOLIVO1 | WWM | REVIEW | Needs Review | |
| 03/27/2006 | AOLIVO1 | ZONING | REVIEW | Needs Review | |
| 03/27/2006 | AOLIVO1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 03/27/2006 | AOLIVO1 | ENGINEERING | REVIEW | Needs Review |