Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T06CM00710
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/06/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM00710 2/6/06 1. Provide electrical design. See the attached Electrical Permitting Requirements. Comments below serve as a guide only, and do not constitute full review. 2. Provide power requirements for the gates. 3. Provide a disconnect per NEC 430 Part IX. 4. Specify conduit and conductor size and type. 5. Specify overcurrent protective devices. 6. Provide voltage, phase, and amperage of new service. 7. Provide TEP available fault current. 8. Show fault current rating of all new equipment. 9. Address equipment grounding per NEC 250 Part VI. 10. Show the grounding electrode system at the service. |
| 02/15/2006 | CAGUILA1 | ZONING | REVIEW | Needs Review | |
| 02/15/2006 | SUZANNE BOHNET | ENGINEERING | REVIEW | Approved |