Permit Number: T06CM00710
Parcel: 118082220

Review Status: Completed

Review Details: OTHER

Permit Number - T06CM00710
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/06/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM00710 2/6/06

1. Provide electrical design. See the attached Electrical Permitting Requirements. Comments below serve as a guide only, and do not constitute full review.
2. Provide power requirements for the gates.
3. Provide a disconnect per NEC 430 Part IX.
4. Specify conduit and conductor size and type.
5. Specify overcurrent protective devices.
6. Provide voltage, phase, and amperage of new service.
7. Provide TEP available fault current.
8. Show fault current rating of all new equipment.
9. Address equipment grounding per NEC 250 Part VI.
10. Show the grounding electrode system at the service.
02/15/2006 CAGUILA1 ZONING REVIEW Needs Review
02/15/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved