Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T06CM00709
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/16/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | t06cm00709 2/16/06 1. Put project address on all electrical sheets. Referring to faxed sheets 02, 03, 04, & 05 from Carole Electric. 2. Provide a scaled drawing which plots the location of the gate operators, the new service pedestal and panel, and the Code-required disconnect within sight of the motor. Questions? Call 791.5550 x1106 or email Linda.Buczynski@tucsonaz.gov. Typical for all such locations. |
| 02/17/2006 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 02/17/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Passed |