Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T06CM00703
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/17/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 04/19/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 04/20/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Minimum font size 1/8". THIS COMMENT WAS MADE ON THE FIRST SUBMITTAL. UNRESPONSIVE. 2. Please reinstate the Branch Circuit Conductor Table, which was removed in the course of Revision 1. 3. New Water Heater is 4.5 KW per Sheet P-01. Is 5.6KW on electrical panel schedule. Please coordinate with Plumbing and clarify. 4. Please assemble two final good sets. |