Permit Number: T06CM00703
Parcel: 12702278B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM00703
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/03/2006 JOSE ORTIZ ENGINEERING REVIEW Approved
02/03/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a riser diagram for the modified waste and vent systems. Reference Section 103.2.3, UPC 2003.
2. Provide a specification for the proposed grease trap. Show how the grease trap and flow control are to be installed. Reference Section 1014.0, UPC 2003.
3. Provide a specification for the new water heater and provide a detail showing how it is to be installed. Show the expansion tank, valves, and T&P relief piping for the water heater. Reference Section 103.2.3, UPC 2003.
02/03/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) PROVIDE JUSTIFICATION / CLARIFICATION THAT THE RESTROOMS ARE FULLY ACCESSIBLE OR PROVIDE BREAKDOWN THAT 20% COST OF CONSTRUCTION IS BEING SPENT TOWARDS ACCESSIBILITY.
2) PROVIDE A DIMENSION OR TO SCALE DRAWING. SPECIFY DIMENSIONS ACCORDING TO ANSI A117.1 2003.
3) CLEAR FLOOR SPACE FOR DOOR AT RESTROOM NUMBER 2 DOOR. IT APPEARS DOOR SWING FOR RESTROOM NUMBER 1 ENCROACHES ON CLEAR FLOOR SPACE. PLEASE JUSTIFY.
02/03/2006 ROBERT SHERRY WATER REVIEW Approved
02/03/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
02/16/2006 GBONILL1 ZONING REVIEW Approved
02/16/2006 GERRY KOZIOL WWM REVIEW Approved
02/16/2006 GBONILL1 FIRE REVIEW Approved
03/03/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied