Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM00703
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/03/2006 | JOSE ORTIZ | ENGINEERING | REVIEW | Approved | |
| 02/03/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a riser diagram for the modified waste and vent systems. Reference Section 103.2.3, UPC 2003. 2. Provide a specification for the proposed grease trap. Show how the grease trap and flow control are to be installed. Reference Section 1014.0, UPC 2003. 3. Provide a specification for the new water heater and provide a detail showing how it is to be installed. Show the expansion tank, valves, and T&P relief piping for the water heater. Reference Section 103.2.3, UPC 2003. |
| 02/03/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) PROVIDE JUSTIFICATION / CLARIFICATION THAT THE RESTROOMS ARE FULLY ACCESSIBLE OR PROVIDE BREAKDOWN THAT 20% COST OF CONSTRUCTION IS BEING SPENT TOWARDS ACCESSIBILITY. 2) PROVIDE A DIMENSION OR TO SCALE DRAWING. SPECIFY DIMENSIONS ACCORDING TO ANSI A117.1 2003. 3) CLEAR FLOOR SPACE FOR DOOR AT RESTROOM NUMBER 2 DOOR. IT APPEARS DOOR SWING FOR RESTROOM NUMBER 1 ENCROACHES ON CLEAR FLOOR SPACE. PLEASE JUSTIFY. |
| 02/03/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 02/03/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 02/16/2006 | GBONILL1 | ZONING | REVIEW | Approved | |
| 02/16/2006 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 02/16/2006 | GBONILL1 | FIRE | REVIEW | Approved | |
| 03/03/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied |