Permit Review Detail
Review Status: Completed
Review Details: SITE
Permit Number - T06CM00697
Review Name: SITE
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/24/2006 | SREEVES1 | FIRE | REVIEW | Denied | Show location of existing fire hydrants. |
| 03/10/2006 | ANDREW CONNOR | NPPO | REVIEW | Denied | 1. A plant professional, such as required under Sec. 3.8.6.7.D shall perform preparation of all elements of the Native Plant Preservation Plan and Application for Exception: A. An arborist certified by the International Society of Arboriculture. B. A landscape architect. C. A horticulturist, biologist, or botanist with a minimum B.A. or B.S. in an appropriate arid environment natural resource field. 2. It appears from photographs submitted with application for exception that native plant species are located on-site, have plant professional verify plant species or submit NPPO plan. |
| 03/10/2006 | ANDREW CONNOR | LANDSCAPE | REVIEW | Denied | 1. The site plan must be accompanied by a landscape plan with information specified in Development Standard 2-07.0. The site plan and landscape plan must show identical site layout to avoid conflict between the two plans. Submit landscape plan with re-submittal. 2. A plant professional, such as required under Sec. 3.8.6.7.D shall perform preparation of all elements of the Native Plant Preservation Plan and Application for Exception: A. An arborist certified by the International Society of Arboriculture. B. A landscape architect. C. A horticulturist, biologist, or botanist with a minimum B.A. or B.S. in an appropriate arid environment natural resource field. 3. It appears from photographs submitted with application for exception that native plant species are located on-site, have plant professional verify plant species or submit NPPO plan. |
| 03/21/2006 | PAUL MACHADO | ENGINEERING | REVIEW | Denied | To: Paul Nzomo DATE: March 21, 2006 Coronado Engineering & Delvelopment, Inc. 1010 N. Finance Center Drive, Ste. 200 Tucson, Arizona 85705 SUBJECT: Pantano Homes, 2491 S. Pantano Pw Site plan T06CM00697 (First Review) T14S, R15E, Section 21 RESUBMITTAL REQUIRED: Site Plan and Drainage Report. The Site Plan (SP) and Drainage Report (DR) cannot be approved as submitted. Please address the following review comments prior to the next submittal. Site Plan: 1. Please include a response letter to the comments along with the corrected copies of the SP. 2. A separate grading plan is required since both the site plan and grading plan are submitted and filed under different City of Tucson activity numbers. 3. Please provide property description per D.S. 2-02.2.1.3. 4. Label existing and future sight visibility triangles per D.S. 2-02.2.1.10. 5. Show all points of egress and ingress including locations and width of driveways and parking area access lanes (P.A.A.L.) per D.S. 2-02.2.1.11. 6. Please label all vehicular, bicycle, pedestrian, and handicapped circulation clearly identified per D.S. 2-02.2.1.12. 7. Show the limits of the 100-year floodplain and water surface elevation per D.S. 2-02.2.1.15. 8. Please provide Drainage patterns and finished grades per D.S. 2-02.2.1.16. 9. Please list estimated cut & fill quantities per D.S. 2-02.2.1.17. 10. Please show dimensioned right-of-way, including any applicable Major Streets and Routes (MS&R) Plan right-of-way per D.S. 2-02.2.1.19. Show the configuration required for the intersection widening of Pantano Parkway. 11. Add the basin(s) maintenance responsibility note per S.M.D.D.F.M. 2.3.1.6 C 1 and 2 to the SP. 12. Dimension from street monument lines to existing and proposed curbs, sidewalks, driveways, and utility lines per D.S. 2-02.2.1.21. 13. Location and orientation of existing major physical features, such as railroad tracks and drainageways per D.S. 2-02.2.1.22. 14. Please provide existing topographic contours at intervals not exceeding two (2) feet and/or spot elevations as pertinent and Bench Mark based on City of Tucson Datum, including City Field Book and page number per D.S. 2-02.2.1.23. Include the datum that was used for the Bench Mark in general note 4, for example: NAVD88 or NGVD 1929. 15. Show all fences, walls, or vegetation for screening and sight visibility by type, material, height, location and spacing per D.S. 2-02.2.1.27. 16. Show Site plan number (T06CM00697) on all sheets per D.S. 2-02.2.1.29. 17. Show refuse container location, size, and access thereto fully dimensioned per D.S. 2-02.2.1.32 and D.S. 6-01.0. Show a detail of the refuse enclosure. Contact Environmental Services @ 791-5543 x1136, John Clark, for refuse enclosure dimensions and requirements. 18. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information. It would be advisable to start a dialog with the Permits and Code section to avoid any conflict with the drainage structures proposed in the R/W. Permits and Codes may not allow the drainage structures in the R/W and this may require a redesign far into the project construction. 19. Please show a typical cross section of the P.A.A.L. or call out the percentage of slopes. Call out the GB at the D/W, if applicable. 20. Please show the proposed roof drainage patterns, 100% of the 10-year flow must be conveyed under the sidewalks including any other site drainage as well. Please provide supporting calculations to demonstrate compliance with D.S. 3-01.4.4. If the location(s) of the roof scuppers have not yet been decided, a general note indicating sidewalk scuppers will be used when the roof scuppers locations have been designed and located will suffice. 21. "A grading permit and Stormwater Pollution Prevention Plans (SWPPP's) will be required for this project. Submit 4 sets of grading and SWPPP's with text, upon completion and submittal of a grading permit application. A grading permit may not be issued prior to site plan approval. Subsequent comments may be necessary, depending upon the nature and extent of revisions that occur to the plans". Drainage Report: 1. Please include a response letter to the comments along with the corrected copies of the DR. 2. This review was performed for Site plan purposes only. Final review and acceptance will done at the grading plan stage. 3. Per the City of Tucson detention/retention manual, this project is subject to the 5-year threshold requirements. 4. In the runoff volume estimator for proposed conditions for the 5-year event is listed as 5,742 cu.ft., however in table 4 on page 9 the combined volume total is 4,250 cu.ft. Revise as required. 5. In section 4.1.2 it is stated that the volume of the detention basin was figured by using the 2 or 5 year event. In all cases of volume of retention needed and/or any other calculations shall be figured using the 5-year event. 6. Show details of all basins with plan views, sections and dimensions in the DR. 7. Include a map showing all drainage patterns in the DR. 8. Demonstrate all-weather access at both entrances. 9. Include an off-site and on-site map showing the drainage areas and the points of discharge from the property in the DR. 10. Please show the proposed roof drainage patterns, 100% of the 10-year flow must be conveyed under the sidewalks including any other site drainage as well. Please provide supporting calculations to demonstrate compliance with D.S. 3-01.4.4. If the location(s) of the roof scuppers have not yet been decided, a general note indicating sidewalk scuppers will be used when the roof scuppers locations have been designed and located will suffice. 11. Show and dimension all depressed curb openings on the drainage map. 12. Include the percolation test results with the next submittal. Grading approval will not be given until test results have been submitted. 13. Add the basin(s) maintenance responsibility note and check list per S.M.D.D.F.M. 2.3.1.6 C 1 and 2 to the DR. 14. Show the project address or administration address on the cover sheet of the DR. If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@tucsonaz.gov Paul P. Machado Senior Engineering Associate City of Tucson/Development Services Department 201 N. Stone Avenue P.O. Box 27210 Tucson, Arizona 85726-7210 (520) 791-5550 x1193 office (520) 879-8010 fax C:/2491 S. Pantano PW Site |
| 04/25/2006 | TERRY STEVENS | ZONING | REVIEW | Denied | DSD TRANSMITTAL FROM: Terry Stevens FOR: David Rivera Lead Planner Principal Planner PROJECT:T06CM00697 2491 S. Pantano Parkway Multi Family Residential Site Plan Transmittal date:1st Review 4/25/06 COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed. 1. DS 2-20.2.1.2 It appears there are five separate lot parcels involved in this project. A lot combination of the parcels and lot combination covenant will be required to be completed before approval of the site plan can be completed. Provide recordation information (docket and page) on the site plan. Lot combination forms can be obtained at the zoning front counter at DSD. Provide the legal description of the property after the lot combination has been completed. 2. DS 2-02.2.1.3 Provide the address of the project on the site plan. 3. DS 2-02.2.1.5 Provide the dimensions of the property line along the west and the east property lines. Indicate as 250.00 feet. 4. DS 2-20.2.1.6 Provide dimensioned building elevations and floor plans in order to verify height of structures and number of bedrooms. These are required in order to complete this review. 5. DS 2-02.2.1.7 As per LUC Sec. 3.2.6.4 in a C1 zone with adjacent commercial zoning and a perimeter yard indicator of "CC" the required perimeter yard setback is the height of the structure. As indicated on the plan the height of the structures are fifteen feet thus requiring a perimeter yard setback of fifteen feet from the property lines on the north, south and east. The plans indicate setbacks from ten feet to ten feet eight inches. 6. DS 2-02.2.1.8 Indicate on the site plan the locations of all wheel stops for the parking spaces. Clearly indicate the required 3' radius, 3' clear space behind and the minimum 24' width for the back up spur located at the southern corner of the property. See DS 3-05 Figure 2. 7. DS 2-02.2.1.9 Off-street bicycle parking, including materials for lighting, paving, and security; fully dimensioned layout; location; specific type of rack and the number of bicycles it supports; and the location and type of directional signage. Provide location of bicycle parking spaces on the site plan as well as a detail of the type of bicycle rack proposed. Directional signage will be required if the parking spaces are not visible from the street. 8. DS 2-20.2.1.10 Provide on the site plan the existing and future sight visibility triangles. See engineering comments. 9. DS 2-02.2.1.12 Clearly indicate the required minimum width of four (4) feet for all sidewalks. The truncated domes indicated at the ramps in the right of way and at the west ramp at the crosswalk are not correct. The domes are to be placed at the bottom of the ramp where the ramp meets the vehicular use area. The truncated domes located at the handicap parking spaces and access aisles are incorrect. If the sidewalk is flush with the pavement in this area a two (2) foot wide strip of domes is required along the sidewalk from ramp to ramp. The handicap signage for the handicap parking spaces cannot be located as indicated on the detail provided. It must be located in an area in which it will not be damaged by vehicles. The detail for the handicap sign is not correct. The height and verbiage of the sign are to be as per Park Wise specifications. Contact Park Wise for criteria on handicap parking signage. 10. DS 2-02..2.1 If applicable, provide the location, type, size and height of all proposed and existing signage including billboards. 11. DS2-02.2.1.19 Provide the future right of way location and future curb location as per the MS&R. See engineering comments. 12. DS 2-02.2.1.20 If applicable provide all easements of record on the site plan together with recording docket and page reference. 13. DS 2-02.2.1.25 If applicable, provide existing and proposed lighting layout and detail of the type of lighting. 14. DS 2-02.2.1.3 In the calculations clearly indicate how the lot coverage percentage has been arrived at. 15. Depending on responses to the above comments and changes to the site plan, further comments may be forth coming. If you have any questions about this transmittal, please call Terry Stevens, (520) 791-5550 ext. 2000. |
| 04/26/2006 | TERRY STEVENS | ZONING HC SITE | REVIEW | Denied | see zoning comments |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/02/2006 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 05/02/2006 | SUE REEVES | REJECT SHELF | Completed |