Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T06CM00672
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/11/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | 1) Third request. Lavatory faucets (including accessible faucets) shall be equipped with a mechanism that causes the faucet to close automatically after delivering no more than one-fourth gallon of water or shall be designed to deliver no more than an average of one-half gallon of water per minute at a pressure of eighty PSI. The maximum flow rates for plumbing fixtures shall be consistent with ARS Title 45, Chapter 1, Article 12. See text at: (http://www.azleg.state.az.us/ArizonaRevisedStatutes.asp). Reference Section 402.1, UPC 2003, as amended by the State of Arizona. Note that Section 606.4, ICC/ANSI A117.1-2003, Accessible and Usable Buildings and Facilities, requires only that hand-operated metering faucets for handicapped accessible lavatories remain on for a minimum of 10 seconds. 2) Sheets P-3 and M-1 show conflicting designs for the domestic hot and cold and hot water. Coordinate the piping sizes with the provided calculations shown on sheets P1 and P2. Reference Section 103.2.3, UPC 1994. Revised (corrected) sheets received 9/18/06 |
| 09/27/2006 | GERRY KOZIOL | WWM | REVIEW | Passed | |
| 10/02/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved |