Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06CM00672
Parcel: 12412293A

Address:
301 S PARK AV

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM00672
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/13/2006 MBROWN3 FIRE REVIEW Approved
02/13/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 2/15/06
ACTIVITY NUMBER: T06CM00672
PROJECT NAME: RESTROOM RENOVATION
PROJECT ADDRESS: 301 S. PARK
ARCHITECT / ENGINEER: MICHAEL BARONE
PROJECT REVIEWER: CHRISTY FOREMAN


TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.

1) Restroom for women's must be 100% accessible the unisex can be provided in addition to the Women's restroom per section 3409.5.
2) Provide vertical grab bar see figure 604.5.1 per ANSI A117.1 2003.
3) Provide signage for restrooms per ANSI A117.1 2003.
4) Clarify ceiling height by providing typical wall section.
5) Clarify that no loading of ceiling deck will occur since it is not designed for carrying loads. Clarify that signage will be posted no loading allowed.
6) Clarify walls and floors in restroom are specified per section 1210.1 and 1210.2 IBC 2003.
02/16/2006 GERRY KOZIOL WWM REVIEW Denied needs 8th floor credit evaluation
02/23/2006 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved
03/15/2006 ROBERT SHERRY WATER REVIEW Approved
03/16/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide descriptions for all plumbing fixtures being provided by others and show that they are in compliance with current material standards. Reference Section 401.1, UPC 2003.
2. Provide specifications (e.g. listing information) for the trap primer. Reference Section 103.2.3, UPC 2003.
3. The maximum flow rates for plumbing fixtures shall be consistent with ARS Title 45, Chapter 1, Article 12. See text at: (http://www.azleg.state.az.us/ArizonaRevisedStatutes.asp). Reference Section 402.1, UPC 2003, as amended by the State of Arizona.
4. Provide a detail of the water heater installation, including the excess pressure relief, expansion tank, and valves. Reference Sections 103.2.3, 605.5, and 608.3 UPC 2003.
5. Provide information to show how the outlet temperature of the hot water is to be limited to 110 degrees at the lavatories. Reference Section 804.3, IECC 2003 and Section 414.1, UPC 2003.
6. If the specified water heater is not supplied with integral heat traps, provide 0.5" of insulation with a maximum conductivity of 0.27 btu per inch/h °F on the first 8 feet of supply and discharge piping. Reference Section 804.4, IECC 2003.
03/16/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/10/2006 AMERY KLAPPERT OUT TO CUSTOMER Completed
04/10/2006 SUE REEVES REJECT SHELF Completed