Permit Number: T06CM00604
Parcel: 13217133D

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM00604
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/31/2006 GERRY KOZIOL WWM REVIEW Needs Review
03/01/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) 20% COST OF CONSTRUCTION NEEDS TO SPENT ON ACCESSIBILITY OR TENANT SPACE NEEDS TO BE 100% COMPLIANT.
2) ACCESSIBLE RESTROOMS WITH DOOR SWINGIN IN CLEAR FLOOR SPACE FOR EACH COMPARTMENT NEEDS TO BE SHOWN SEE 604.9.3 ANSI A117.1 2003. COMPARTMENT DOOR NEXT TO ACCESSIBLE COMPARTMENT CANNOT SWING INTO CLEAR FLOOR SPACE.
3) PLEASE CLARIFY DISTANCE TRAVELED ON INTERIOR ACCESSIBLE PATH.
4) PROVIDE VERTICAL GRAB BAR FOR ACCESSIBLE COMPARTMENT.
03/01/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
03/01/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
03/01/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved