Permit Number - T06CM00604
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/30/2006 | MBROWN3 | FIRE | REVIEW | Approved | |
| 01/30/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The current plumbing code is the 2003 UPC with local amendments. 2. Provide an upper terminal cleanout for the new restrooms (detail 1/P1). Reference Section 707.4, UPC 2003. 3. A 3/4" copper runout to the urinal will result in a velocity exceeding 8 FPS (urinal flush valves require approximately 15 GPM to operate). Reference Section 610.0, IAPMO IS 3-93. |
| 01/30/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 01/30/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. The minimum required ventilation for a restroom is 75 CFM per water closet or urinal. Reference Section 403.3, IMC 2003. 2. Show how the restroom exhaust fans will be controlled to prevent recirculation of the supply air from the restrooms. Reference Section 403.2, IMC 2003. |
| 01/31/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) Provide dimensions on floor plan for restroo facilities along with clear floor space envelopes. 2)It appears doors along corridor are not accessible. |
| 01/31/2006 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 01/31/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM00604 1/31/06 1. Provide fixture schedule for new lighting. 2. Specify the NEC 2002, not the latest published edition. City of Tucson does not yet enforce NEC 2005. |
| 01/31/2006 | SUZANNE BOHNET | ENGINEERING | REVIEW | Approved | |
| 03/01/2006 | AOLIVO1 | WWM | REVIEW | Needs Review |