Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T06CM00532
Parcel: 131050030

Address:
5472 E 29TH ST

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T06CM00532
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/27/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
06/28/2006 JWILLIA5 ELECTRICAL-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/28/2006 ADRIANNE OLIVO OUT TO CUSTOMER Completed