Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T06CM00527
Parcel: 111083580

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM00527
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/24/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved Community Room not located in the Zone AH - no shared entryway with building that is located in Zone AH.
01/24/2006 MICHAEL ST. PAUL ZONING REVIEW Approved
01/25/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
01/25/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) CLARIFY OCCUPANCY OF ROOM. CLARIFY OCCUPANT LOAD.
2) PROVIDE ACCURATE CODE ANALYSIS.
3) TEMPERED GLASS IN WINDOWS PER CODE SECTION 2406.3.
4) CLARIFY REMOVAL OF WINDOW FRAME NOTE 5 DEMOLITION PLAN AND REPLACEMENT ON FLOOR PLAN.
5) CLARIFY SPECIFY RELOCATION OF POOL EQUIPMENT.
6) PROVIDE CLEAR FLOOR SPACE FOR WATER CLOSET AND LAVATORY PER ANSI 2003 A117.1.
01/25/2006 ROBERT SHERRY WATER REVIEW Approved
01/25/2006 JIM EGAN FIRE REVIEW Approved
01/25/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
01/25/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM00527 1/25/06

1. Provide panel and circuit number for new 20A Ckt.
2. Provide schedule for new lighting fixture.
3. It shall be clear from the plans that the panel powering the new circuit is not overloaded.
02/03/2006 GBONILL1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
02/03/2006 GBONILL1 OUT TO CUSTOMER Completed