Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06CM00468
Parcel: 11714337H

Address:
334 W 18TH ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM00468
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/16/2006 WILDAN 2ND PARTY REVIEW REVIEW Denied May 12, 2006

Development Services Department
City of Tucson
P.O. Box 27210
Tucson, AZ 85726


RE: LOVEGROVE/COX RESIDENCE – 2ND REVIEW
CITY OF TUCSON LOG NO. T04CM00468
WILLDAN PLANCHECK NO. 13881-6002

The second review for the above project has been completed. This letter contains comments which need to be addressed by written responses to each which indicate any actions taken. In order to facilitate a shorter third review, all corrections and revisions must be made on the original plans and two complete new sets of prints, along with one complete redlined set, must be returned to our office. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets, and that all changes have been highlighted with appropriate revision numbers, revision dates, and “cloud bubbles.” Pen or pencil corrections on final prints are not acceptable.

This project has been reviewed for conformance with the 2003 IRC, 1997 UAC, 2003 IMC, 2003 IECC, 2002 NEC codes with local modifications, and the 2003 UPC with State of Arizona Amendments. Any revisions to this plan will require an additional review and approval by Willdan.

Should you have questions regarding the comments herein, please contact your plans examiner Antonio Moya.


Occupancy
Occup. Load
Construction
Area S.F.
Sprinklered
Alarms

SFR
Garage
Porch

N/A

V-B
2703
901
437

No

Smoke

GENERAL COMMENTS:
Reviewed and accepted.

ARCHITECTURAL COMMENTS:
Reviewed and accepted.

STRUCTURAL COMMENTS:
Reviewed and accepted.

PLUMBING COMMENTS:
Sheet P1
(New Comment) Provide the total fixture unit demand and maximum developed length of the waterline. Reference 2003 UPC Table 6-4 and City of Tucson Submittal Requirements. The 2003 IRC is being referenced. Please correct.

(Comment Not Addressed) The City of Tucson will accept the 2003 Uniform Plumbing Code with its amendments. All plans must reference the 2003 in its entirety. Please comply and revise plans accordingly. Revise all references to the 2003 UPC.

MECHANICAL COMMENTS:
Reviewed and accepted.

ELECTRICAL COMMENTS:
Sheet E1
(Comment Not Addressed) Please provide cut sheets for all the exterior light fixtures shown or noted on the plans. The cut sheets must provide lumens per fixture. The cut sheets need to show if the fixture is a full cut off, which means no light is emitted at or above the horizontal plane. Please provide calculations as well. Reference City of Tucson Outdoor Lighting Code.

ENERGY CODE COMMENTS:
Reviewed and accepted.

ACCESSIBILITY COMMENTS:
N/A

Sincerely,

WILLDAN




Martin Haeberle, C.B.O.
Building Official

MAH/tb
05/17/2006 GERRY KOZIOL WWM REVIEW Denied NEEDS WASTEWATER 8TH FLOOR REVIEW OF CONNECTION TO MAIN STREET WITH JT USE AGREEMENT & EASEMENT

Final Status

Task End Date Reviewer's Name Type of Review Description
05/18/2006 ADRIANNE OLIVO OUT TO CUSTOMER Completed
05/18/2006 GBONILL1 REJECT SHELF Completed