Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T06CM00375
Parcel: 140152700

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM00375
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/16/2006 BROWN & ASSOCIATES 2ND PARTY REVIEW REVIEW Denied Brown & Associates
177 N Church Avenue, Suite 311
Tucson, Arizona 85701
Office (520) 882-4735 Fax (520) 882-5412


4th - Review
RESIDENTIAL PLAN REVIEW

Client: City of Tucson Reviewer: L. Pudvah

Project: Mendoza Addition Permit #: T06 CM00375

Date: 15 June 2006 Brown & Associates #: 85701-6212

_______________________________________________________________

2003 International Residential Code, 2003 UPC with State Amendments, Outdoor Lighting Code; 2003 IBC applies for engineered structural designs.

Residence Area: S.F. Number of Floor Levels: 1
Enclose Carport Area: 254 S.F. Additional # of Elevation Options: n/a
Porch/Stair/Deck Area: n/a S.F. Building Wall Construction: Wood/Masonry
Basement Level Area: n/a S.F. Building Grade Floor Construction: S.O.G.
Guest House Area: n/a S.F. Building Roof Construction: Wood
Guest House Construction: n/a Elevated Floor Construction: n/a
Add Bathroom Area: 55 S.F.


NOTE: THE FOLLOWING ITEMS NEED TO BE CORRECTED PRIOR TO RESUBMITTING YOUR PLANS FOR APPROVAL. RETURN ALL SUBMITTAL PLANS AND DOCUMENTS WITH YOUR REVISED SUBMITTAL PLANS AND DOCUMENTS. . Highlighted comments are in response to the applicant’s response and resubmittal. THE PLANS NEED TO BE LEGIBLY PREPARED IN ACCORDANCE WITH THE CITY OF TUCSON STANDARD.
Revise Plans for Compliance
IRC Section R105.3.1



STRUCTURAL FOUNDATION PLAN COMMENTS:


1. Provide a continuous exterior footing at the enclosed carport and indicate pressure treated plate and anchor bolt requirements. IRC Chapter 4. Anchor bolts for wood sill plates shall be ½-inch diameter with a minimum embedment of 7-inches into the new cast in place concrete footing. All footings shall be clearly dimensioned and depicted to be bearing not less than 12-inches below undisturbed grade. R403.1.6, R403.1.4


STRUCTURAL FRAMING PLAN COMMENTS:

1. Identify and specify structural sheathing for walls, floors and roofs. R503, R604, R803 It is not clear what if any structural sheathing is being installed under the new siding. A weather resistive building paper must be specified to protect the interior of the building. The new end wall must be shown to meet the requirement for braced wall shear panels. The new end wall shall be sheathed with not less than ½ -inch OSB or wood plywood and nailed as required. R602.10.1.1

2. It is not clear what is suppose to be holding up the existing 4x8 over the new window in the enclosed carport. All structural member sizes shall be shown on a dimensioned plan that identifies and depicts the length of member spans, spacings, location and sizes of all rafters, headers, posts and beams. IRC 106.1.1 Sections R602.7, R603.9, R606.9. It appears that an appropriate header beam and jack studs are required to support the end reaction for the existing roof beam which is shown over the new window. Review and clarify design. R502.5

3. Identify that all code required nailing to comply with IRC Table R602.3(1).




Sincerely,

BROWN & ASSOCIATES



Michael J. Brown, C.B.O. President
MB:jh

Final Status

Task End Date Reviewer's Name Type of Review Description
06/19/2006 SUE REEVES OUT TO CUSTOMER Completed
06/19/2006 SUE REEVES REJECT SHELF Completed