Permit Number: T06CM00371
Parcel: 13329001A

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T06CM00371
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/25/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 1/25/06
ACTIVITY NUMBER: T06CM00371
PROJECT NAME: T-Mobile - Cell site
PROJECT ADDRESS: 545 N. Camino Seco
ARCHITECT / ENGINEER:
PROJECT REVIEWER: Christy Foreman


TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.

1) Provide structural design for pole or shop drawings for pole.
2) Provide detail connections of ball field lights.
3) Provide detail of connection for grip strut top cover.
4) Clarify / detail termination frame for electrical equipment.
01/28/2006 DAN CASTRO PLANNING-CITY HALL REVIEW Approved
02/02/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM00371 1/20/06, AND 2/2/06
Reference New Ballfield Lights Sheet A-3. Demonstrate compliance with the Tucson Lighting Code. Provide lighting fixture cut sheets. Clarify number of lighting fixtures to be installed on new pole. Identify panel and circuit number. Clarify electrical load characteristics. Specify how the Contractor is to bring power to the lights.

Complete panel schedule.
02/09/2006 PAUL MACHADO ENGINEERING REVIEW Approved
02/17/2006 JAY HOGAN COMMUNICATIONS REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/14/2006 AOLIVO1 OUT TO CUSTOMER Completed
03/14/2006 SUE REEVES REJECT SHELF Completed