Permit Number: T06CM00371
Parcel: 13329001A

Review Status: Completed

Review Details: PLANS OK TO SUBMIT - COMM

Permit Number - T06CM00371
Review Name: PLANS OK TO SUBMIT - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/20/2006 HEATHER THRALL ZONING REVIEW Passed
01/20/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM00371 1/20/06
Reference New Ballfield Lights Sheet A-3. Demonstrate compliance with the Tucson Lighting Code. Provide lighting fixture cut sheets. Clarify number of lighting fixtures to be installed on new pole. Identify panel and circuit number. Clarify electrical load characteristics. Specify how the Contractor is to bring power to the lights.

Complete panel schedule.
01/20/2006 JIM EGAN FIRE REVIEW Approved
01/20/2006 RAUL PALMA BUILDING-COMMERCIAL REVIEW Needs Review
01/20/2006 ANY ENGINEERING REVIEW Approved