Permit Review Detail
Review Status: Completed
Review Details: PLANS OK TO SUBMIT - COMM
Permit Number - T06CM00371
Review Name: PLANS OK TO SUBMIT - COMM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/20/2006 | HEATHER THRALL | ZONING | REVIEW | Passed | |
| 01/20/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM00371 1/20/06 Reference New Ballfield Lights Sheet A-3. Demonstrate compliance with the Tucson Lighting Code. Provide lighting fixture cut sheets. Clarify number of lighting fixtures to be installed on new pole. Identify panel and circuit number. Clarify electrical load characteristics. Specify how the Contractor is to bring power to the lights. Complete panel schedule. |
| 01/20/2006 | JIM EGAN | FIRE | REVIEW | Approved | |
| 01/20/2006 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 01/20/2006 | ANY | ENGINEERING | REVIEW | Approved |