Permit Number: T06CM00370
Parcel: 11520198A

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T06CM00370
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/25/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 1/25/06
ACTIVITY NUMBER: T06CM00370
PROJECT NAME: T-Mobile - Cell site
PROJECT ADDRESS: 1400 N. Silverbell
ARCHITECT / ENGINEER: Kenneth D. Camp
PROJECT REVIEWER: Christy Foreman


TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.

1) Provide structural design for pole or shop drawings for pole.
2) Provide detail / section for 10 ft. chain link fence. Clarify how it will be installed.
3) Detail connection of existing lights on light pole.
4) Clarify / detail termination frame for electrical equipment.
01/25/2006 DAN CASTRO PLANNING-CITY HALL REVIEW Denied Plans may not be approved until the City Of Tucson has approved the lease agreement. Provide a copy of the lease agreement with the plans. For infomation on the lease agreement please contact Dave Koss with the Real Estate Division of the City of Tucson Transportation Department.
01/25/2006 DAN CASTRO ZONING REVIEW Denied Plans may not be approved until the City Of Tucson has approved the lease agreement. Provide a copy of the lease agreement with the plans. For infomation on the lease agreement please contact Dave Koss with the Real Estate Division of the City of Tucson Transportation Department.
01/27/2006 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved
02/02/2006 JAY HOGAN COMMUNICATIONS REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/17/2006 JMORALE1 OUT TO CUSTOMER Completed
02/17/2006 SUE REEVES REJECT SHELF Completed