Permit Number - T06CM00370
Review Name: PLANS OK TO SUBMIT - COMM
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/20/2006 | HEATHER THRALL | ZONING | REVIEW | Needs Review | |
01/20/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM00370 1/20/06 Clarify number of lighting fixtures to be removed and reinstalled on new pole. Identify panel and circuit number. Clarify electrical load characteristics. Is this the Tech LIght on Ckt 24? Specify how the Contractor is to bring power to the relocated lights. |
01/20/2006 | JIM EGAN | FIRE | REVIEW | Approved | |
01/20/2006 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
01/20/2006 | ANY | ENGINEERING | REVIEW | Approved |