Permit Number: T06CM00343
Parcel: 137010020

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM00343
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/10/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Indicate the thickness of the existing slab (10" embedment required for the expansion bolts).
2. The placement of the pipe supports at the east end of the piping is constraining the movement of the pipe. Does this consraint overstress the fitting?
3. Note #4 of detail 2/M2.1 calls for a 3/8"x10"x10" base plate but the detail calls out a 3'-4"x3'-4" base plate with the expansion bolts located 6" from the edge of the plate. Please clarify the dimensions of the plate and the bolt locations.
02/16/2006 DROBEY1 WWM REVIEW Passed