Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/10/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Indicate the thickness of the existing slab (10" embedment required for the expansion bolts). 2. The placement of the pipe supports at the east end of the piping is constraining the movement of the pipe. Does this consraint overstress the fitting? 3. Note #4 of detail 2/M2.1 calls for a 3/8"x10"x10" base plate but the detail calls out a 3'-4"x3'-4" base plate with the expansion bolts located 6" from the edge of the plate. Please clarify the dimensions of the plate and the bolt locations. |
02/16/2006 | DROBEY1 | WWM | REVIEW | Passed |