Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06CM00332
Parcel: 20914001C

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T06CM00332
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/27/2006 ROBERT SHERRY WATER REVIEW Denied Show the location of the reduced pressure backflow assembly on the drawings, specify the reduced pressure backflow assembly being installed, and indicate the size of the assembly. Reference City of Tucson Ordinance 9976, Backflow Prevention and Cross-connection Control.
03/27/2006 MARTIN BROWN FIRE REVIEW Denied Additional fire hydrant required per City of Tucson amendment to the 2003 IFC, Section 508.5.1
03/28/2006 AKLAPPE1 ZONING REVIEW Needs Review
03/28/2006 AKLAPPE1 WWM REVIEW Needs Review
03/28/2006 AKLAPPE1 ENGINEERING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
03/28/2006 AMERY KLAPPERT OUT TO CUSTOMER Completed