Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T06CM00244
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/20/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | t05cm00244 1/20/06 1. "c" value used for fault calculation, 23600, does not correspond to 600-750 MCM Al in nonmagnetic conduit. Not suitable for 900 MCM. suggest the use of 28779. Fault #1. 2. Fault calculation #1 does not take into consideration quantity 4 parallel conduits. 3. Suggest the use of 75,100A as a starting point, per TEP published data, unless their Representative has confirmed differently. 4. Fault calculations use 208V. The system is at 240V. |