Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06CM00244
Parcel: 12106261C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM00244
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/18/2006 JIM EGAN FIRE REVIEW Approved
01/18/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM00244 1/18/06

A crosscheck of fault calculations yeilded different values than that on the plans. Fundamentally, the service was shown separate from the building, which may be doubtful. But the backcheck was done using the 6' distance between the utility transformer and the building service as plotted on the scaled drawing. This yeilded a result of 72729A available at the service, considering 4 parallel 900 MCM aluminum, which clearly does little to attenuate fault current. Then, 44' were taken to the new panel using non-metallic conduit with the resultant of 27991A of AFC. Please revisit the fault calculations, and account for true distances, and size and cross-sectional area of conductors. Also please double-check the exact location of the transformer and building service.