Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM00244
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/13/2006 | SUZANNE BOHNET | ENGINEERING | REVIEW | Approved | |
| 01/13/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 01/13/2006 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 01/13/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 01/13/2006 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 01/13/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 01/13/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM00244 DENIED 01/13/06 1. Show location of New Panel A, and electrical service, on plans. 2. Provide available fault current at service. 3. Provide fault calculations for new panel. |
| 01/18/2006 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 01/18/2006 | JMORALE1 | FIRE | REVIEW | Needs Review |