Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T06CM00199
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/06/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 03/07/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. If AC-1 is located as shown on sheet M1, provide guards for equipment (it is located within 10 feet of a roof edge or of a walking surface that is elevated more than 30 inches above the adjoining grade). Reference Section 304.10, IMC 2003. (Also, where are AC-2 and AC-3, shown on the heat pump schedule, located?) 2. If AC-1 is located as shown on sheet A1, show that a separation of at least ten feet exists between air intake openings and exhaust openings. Reference 401.5, IMC 2003. |
| 03/16/2006 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/23/2006 | GBONILL1 | OUT TO CUSTOMER | Completed |
| 03/23/2006 | SUE REEVES | REJECT SHELF | Completed |