Permit Number: T06CM00199
Parcel: 120086920

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM00199
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/06/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
03/07/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. If AC-1 is located as shown on sheet M1, provide guards for equipment (it is located within 10 feet of a roof edge or of a walking surface that is elevated more than 30 inches above the adjoining grade). Reference Section 304.10, IMC 2003. (Also, where are AC-2 and AC-3, shown on the heat pump schedule, located?)
2. If AC-1 is located as shown on sheet A1, show that a separation of at least ten feet exists between air intake openings and exhaust openings. Reference 401.5, IMC 2003.
03/16/2006 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/23/2006 GBONILL1 OUT TO CUSTOMER Completed
03/23/2006 SUE REEVES REJECT SHELF Completed