Permit Number: T06CM00191
Parcel: 10819224A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM00191
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/11/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) WORK STATION PLEASE JUSTIFY PER ANSI A117.1 2003 SECTION 904.3.
01/11/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
01/11/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM000191 01//11/06

1. Show the location of service, on scaled drawings.
2. Indicate fault current at service, and provide fault calculations for New Panel. Verify that the 10K rating is sufficient for AFC.
3. Demonstrate compliance with the 2003 IECC.
4. If fusing for FC4 and FC6 are intended for overload protection, it appears that they should be 6A and 10A respectively. If sized per manufacturer's requirements, disregard.
01/11/2006 ROBERT SHERRY WATER REVIEW Approved
01/11/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
04/07/2006 DROBEY1 FIRE REVIEW Needs Review
04/07/2006 DROBEY1 WWM REVIEW Needs Review
04/07/2006 DROBEY1 ZONING REVIEW Needs Review
04/07/2006 DROBEY1 ENGINEERING REVIEW Needs Review