| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/11/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) WORK STATION PLEASE JUSTIFY PER ANSI A117.1 2003 SECTION 904.3. |
| 01/11/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 01/11/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM000191 01//11/06 1. Show the location of service, on scaled drawings. 2. Indicate fault current at service, and provide fault calculations for New Panel. Verify that the 10K rating is sufficient for AFC. 3. Demonstrate compliance with the 2003 IECC. 4. If fusing for FC4 and FC6 are intended for overload protection, it appears that they should be 6A and 10A respectively. If sized per manufacturer's requirements, disregard. |
| 01/11/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 01/11/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 04/07/2006 | DROBEY1 | FIRE | REVIEW | Needs Review | |
| 04/07/2006 | DROBEY1 | WWM | REVIEW | Needs Review | |
| 04/07/2006 | DROBEY1 | ZONING | REVIEW | Needs Review | |
| 04/07/2006 | DROBEY1 | ENGINEERING | REVIEW | Needs Review |