Permit Number: T06CM00186
Parcel: 11931013C

Review Status: Completed

Review Details: OTHER

Permit Number - T06CM00186
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/14/2006 HEATHER THRALL ZONING REVIEW Approved
03/14/2006 JOSE ORTIZ ENGINEERING REVIEW Approved
04/19/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM00186 4/19/06

1. On Sheet 2, demonstrate compliance with NEC 110.26 Working Clearance.
2. Panel layout on roof does not conform to the configuration in the line diagram on the model plans. In order to use the model plans, an Electrical Engineer registered in the State of Arizona shall diagram the new configuration of row boxes and panels.