Permit Number: T06CM00186
Parcel: 11931013C

Review Status: Completed

Review Details: OTHER

Permit Number - T06CM00186
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/14/2006 JOSE ORTIZ ENGINEERING REVIEW Approved
03/15/2006 KKARSEN1 ELECTRICAL-COMMERCIAL REVIEW Denied T06CM00186 3/15/06

1. It appears that the intent is to use TEP model plans. If such is the case, Applicant shall submit two sets of the actual model(s) intended for use. These shall be obtained from the Tucson Electric Power Company.
2. Put address on all plans which are not part of the model plan set.
3. Provide location of all new and existing equipment on plan view.
4. Interconnection diagram shows 18 photovoltaic panels. Site plan shows 40 such panels. Clarify scope of work.
5. Please number all pages not part of the model plans.
6. Please clarify intent of the Sheet entitled "Overhead Service Entrance."
7. Provide an electrical line diagram showing the connection specific to this site, including but not limited to the rating of any Customer Main Service Panel and it Main overcurrent protective device.
03/15/2006 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Approved