Permit Number: T06CM00145
Parcel: 13323190A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM00145
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/10/2006 JIM EGAN FIRE REVIEW Approved
01/10/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
01/10/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM00145 01/10/06

1. Provide panel and circuit numbers for all new receptacles. Demonstrate that no panel is overloaded with the additional receptacles.
01/10/2006 ROBERT SHERRY WATER REVIEW Approved
01/10/2006 MICHAEL ST. PAUL ZONING REVIEW Approved
01/10/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
01/10/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved
02/14/2006 DROBEY1 WWM REVIEW Passed
02/14/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved