Permit Number: T06CM00144
Parcel: 13317064C

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T06CM00144
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/02/2006 ROBERT SHERRY WATER REVIEW Approved
03/02/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. A revision to the project is not the same as a new project. Include the plans, schedules, and riser diagrams for the original project on the revised drawings. Provide information to show that the existing water service is not overloaded.
2. The trap arms for P-3 and P-4 shall be the same size as the traps for those fixtures.
03/02/2006 PATRICIA GILBERT ENGINEERING REVIEW Approved
03/02/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
03/02/2006 MICHAEL ST. PAUL ZONING REVIEW Approved
03/02/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
03/02/2006 JWILLIA5 BUILDING-COMMERCIAL REVIEW Approved
03/10/2006 DROBEY1 WWM REVIEW Needs Review
03/10/2006 DROBEY1 FIRE REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
03/10/2006 DELMA ROBEY OUT TO CUSTOMER Completed