Permit Number: T06CM00144
Parcel: 13317064C

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM00144
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/01/2006 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
02/01/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the ventilation calculations to include the effect of a common supply to the different occupancies. Reference Section 403.3.2, IMC 2003.
02/01/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
02/07/2006 JMORALE1 WWM REVIEW Needs Review