Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T06CM00144
Parcel: 13317064C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM00144
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/10/2006 JOSE ORTIZ ENGINEERING REVIEW Approved
01/10/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The current plumbing code is the 2003 UPC.
2. Show how the building drain and the waste branches are related to the relocated fixtures (i.e. a riser diagram)
3. The minimum flowing pressure for the Haws model 7612 eyewash is 30 PSI. Show how the existing water distribution system is able to accomodate this requirement..
4. Show how the existing CW and HW piping is being modified.
01/10/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
01/10/2006 ROBERT SHERRY WATER REVIEW Approved
01/10/2006 PATRICIA GEHLEN ZONING REVIEW Approved
01/10/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide outside air calculations and show the balancing information on the drawing.
02/01/2006 DROBEY1 BUILDING-COMMERCIAL REVIEW Needs Review 1) Provide a more complete floor plan. It appears existing
corridor is being blocked.
02/01/2006 DROBEY1 WWM REVIEW Needs Review
02/01/2006 JIM EGAN FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/01/2006 DELMA ROBEY APPROVAL SHELF Completed
02/01/2006 DELMA ROBEY OUT TO CUSTOMER Completed
02/01/2006 DELMA ROBEY REJECT SHELF Completed