Permit Number: T06CM00112
Parcel: 126062370

Address:
4218 E IRVING CI

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM00112
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/01/2006 BROWN & ASSOCIATES 2ND PARTY REVIEW REVIEW Denied Brown & Associates
177 N Church Avenue, Suite 311
Tucson, Arizona 85701
Office (520) 882-4735 Fax (520) 882-5412


RESIDENTIAL PLAN REVIEW

Client: City of Tucson Reviewer: L. Pudvah

Project: Mitchell/Morland Residence Permit #: T06CM00112

Date: 28 February 2006 Brown & Associates #: 85701-6206

_______________________________________________________________

2003 International Residential Code, 2003 UPC with State Amendments, Outdoor Lighting Code. 2003 IBC for engineered structural design.

Residence Addition: 432 S.F. Number of Floor Levels: 1
Garage Area: n/a S.F. Number of Elevation Options: n/a
Porch/Deck Area: 438 S.F. Building Wall Construction: Wood/Masonry
Basement Level Area: n/a S.F. Building Grade Floor Construction: S.O.G.
Remodel Existing Area: 447 S.F. Building Roof Construction: Wood Trusses
Guest House Construction: n/a Elevated Floor Construction: n/a
NOTE: THE FOLLOWING ITEMS NEED TO BE CORRECTED PRIOR TO RESUBMITTING YOUR PLANS FOR APPROVAL. RETURN ALL SUBMITTAL PLANS AND DOCUMENTS WITH YOUR REVISED SUBMITTAL PLANS AND DOCUMENTS. . Highlighted comments are in response to the applicant’s reply. .
X Revise Plans for Compliance
IRC Section R105.3.1
GENERAL REQUIREMENTS:

X 1. Show all utilities on the required site plan. Identify on the site plan the routing for the existing water supply from the water meter to the entrance into the existing house. IRC Section R106.1.1.




2. Construction details provided for Building Safety approval should be represented and detailed on the drawings and not specified by code reference only. CODE section references only are not acceptable when specific construction details are needed to convey and distinguish what it is the constructor is suppose to actually supply and install to fulfill the substance and quality for the design. R106.1.1


ARCHITECTURAL PLAN COMMENTS


X 1. Coordinate the architectural dimensioning of building walls to incorporate all
required braced wood stud walls and masonry shear walls in the longitudinal and transverse directions. IRC R602.10.1.1, R606.1.1; ACI-530-02 Chapter 5

ARCHITECTURAL BUILDING ELEVATION COMMENTS:


X 1. Provide drawing details that identify specific (materials, size, type, spacings, gage, etc.) exterior wall veneer anchoring method, backing, flashing and support . (ICBO Evaluation Report number if applicable). IRC Section R703.7.2, R703.7.4


ARCHITECTURAL BUILDING CROSS SECTION COMMENTS:


X 1. Identify, depict and specify requirements for fire blocking. Show specific location details on the drawings where it is required. IRC Section R602.8, R502.1.3.


MODEL ENERGY CODE COMMENTS

X 1. Identify on the drawing the required insulation SHGC for all glazing and U-value for all glazing in windows and or glazing for doors. IRC Section N1102.1, N1102.2

X 2. Identify on the mechanical drawing the required insulation (1.25 inch insulation thickness for exterior piping and 0.75 inch insulation thickness for interior piping) for mechanical systems piping. IRC Section N1103.5

X 3. Identify on the mechanical drawing the required HVAC system controls. The existing thermostat is not identified on the drawing or in the legend. IRC Section N1103.2

X 4. Recessed Type IC rated lighting fixtures shall be clearly noted and specified on the drawings. The construction surrounding a recessed lighting fixture installation that utilizes a non-IC rated fixture shall be depicted and shown completely on the drawings. N1102.1.11






STRUCTURAL FOUNDATION and FRAMING PLAN COMMENTS:

X 1. The proposed removal of existing perimeter masonry building walls and the propose reframing of the existing structure and its supports and the expansion of roof diaphragm coupled with incorporating new wood stud shear walls for lateral support of the remodeled existing masonry wall building construction is not within the prescriptive requirements of applicable IRC Sections or the empirical design of masonry. The proposed remodel and incorporation of new wood components shall be designed and coordinated by a registrant engineer and applicable design structural calculations shall be submitted. Structural plans and details shall be sealed by the registrant engineer. R106.1, R301.1.3, R403, R602.10.10, R606.1.1, R802.10.4, R802.10.5; ACI-530-02

X 2. Indicate all braced wall panel and masonry shear wall locations. Specify the method of bracing and materials to be used. A sealed lateral analysis, prepared by an Arizona Registrant shall be provided. R106.1, R301.1.3

MECHANICAL PLAN COMMENTS:

X 1. Provide combustion air for all liquid and solid fuel-burning appliances including size, type, and location of openings (Identify placement of High & Low combustion air openings). IRC Chapter 1701 and G2406.2, UPC 507.

PLUMBING PLAN COMMENTS


X 1. Identify the total developed length of gas piping, BTUH gas demand of all appliances and provide suitable gas isometric (coordinated with the plan) showing the length of pipes (horizontal and vertical) to each appliance and required size of existing and new gas pipes. R106.1.1, UPC 1217


OUTDOOR LIGHTING CODE:


X 1. Provide on the drawing appropriate tabular calculations that identify Outdoor Lighting Code site designation, total site area, allowable lumens per Table 5.1, conditions for installation of outdoor lighting fixture type, total lumens allowed at the site, maximum unshielded lumens at the site, and the actual installed lumens at the site for each fixture type. The applicant’s reply referencing an exemption in Section 5.1B is not understood since that section does not seem to be evident in adopted outdoor lighting code. Review and clarify. (See illustration attached to sheet A8)


Sincerely,

BROWN & ASSOCIATES



Michael J. Brown, C.B.O. President
MB:ns

Final Status

Task End Date Reviewer's Name Type of Review Description
03/02/2006 CINDY AGUILAR OUT TO CUSTOMER Completed
03/02/2006 SUE REEVES REJECT SHELF Completed