Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/WWM
Permit Number - T06CM00112
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/10/2006 | BROWN & ASSOCIATES | 2ND PARTY REVIEW | REVIEW | Denied | Brown & Associates 177 N Church Avenue, Suite 311 Tucson, Arizona 85701 Office (520) 882-4735 Fax (520) 882-5412 RESIDENTIAL PLAN REVIEW Client: City of Tucson Reviewer: Jake Hesselgesser Project: Mitchell/Morland Residence Permit #: T06CM00112 Date: February 8, 2006 Brown & Associates #: 85701-6206 _______________________________________________________________ 2003 International Residential Code, 2003 UPC with State Amendments, Outdoor Lighting Code. Residence Area: 1853 S.F. Number of Floor Levels: 1 Garage Area: n/a S.F. Number of Elevation Options: 1 Porch/Deck Area: 380 S.F. Building Wall Construction: Wood/Masonry Basement Level Area: n/a S.F. Building Grade Floor Construction: S.O.G. Guest House Area: n/a S.F. Building Roof Construction: Wood Trusses Guest House Construction: n/a Elevated Floor Construction: n/a NOTE: THE FOLLOWING ITEMS NEED TO BE CORRECTED PRIOR TO RESUBMITTING YOUR PLANS FOR APPROVAL. RETURN ALL SUBMITTAL PLANS AND DOCUMENTS WITH YOUR REVISED SUBMITTAL PLANS AND DOCUMENTS. . X Revise Plans for Compliance IRC Section R105.3.1 GENERAL REQUIREMENTS: X 1. Indicate the effective code editions adopted by the City of Tucson on the front cover of the plans. IRC R106.1.1 X 2. Show all utilities on the required site plan. IRC Section R106.1.1. ARCHITECTURAL PLAN COMMENTS X 1. Specifically identify on the plans or elevations those glazing panes which must be tempered glazing. IRC Section R308.4. X 2. An attic access opening shall be provided to attic areas that exceed 30 square feet and have a vertical height of 30 inches and 30 square-feet area or greater. The rough-framed opening shall not be less than 22 inches by 30 inches and shall be located in a hallway or other readily accessible location. A 30-inch minimum unobstructed headroom in the attic space shall be provided at some point above the access opening. IRC Section R807.1. X 3. Identify flame and smoke index for thermal insulations. R316, R906 X 4. Provide attic ventilation calculations for all concealed attic spaces; include required and provided net free ventilation area. Indicate the size, type, wire mesh and location of attic ventilation. Provide the following note, if applicable: "Where eave or cornice vents are installed insulation shall not block the free flow of air. A minimum of 1 inch space shall be provided between the insulation and roof sheathing at the location of the vent”. IRC Section R806. ARCHITECTURAL BUILDING ELEVATION COMMENTS: X 1. Provide exterior wall veneer anchoring method, backing and support. (ICBO Evaluation Report number if applicable). IRC Section R703.7.2, R703.7.4 ARCHITECTURAL BUILDING CROSS SECTION COMMENTS: X 1. Identify, depict and specify requirements for fire blocking. IRC Section R602.8, R502.1.3. ARCHITECTURAL ROOF PLAN COMMENTS: X 1. Depict and show all roof slopes (i.e.: patio roof). R106.1.1, R903.4, UPC Appendix D. ARCHITECTURAL CHIMNEY & FIREPLACE REQUIREMENTS: X 1. Factory built fireplaces and chimneys (zero-clearance) shall be listed by an approved listing agency. Specify make and model number and provide the approval number of the testing agency. The manufacturer’s installation instructions shall be posted at the job site. R1002.1, R1004.1 MODEL ENERGY CODE COMMENTS X 1. Provide on the architectural drawings a calculation to determine the percentage of glazing in the gross area of the exterior walls. Calculations to verify compliance with the jurisdiction’s adopted Energy Conservation Code are required when the glazing area of a detached dwelling exceeds 15-percent of the gross area of the exterior walls. IRC Section N1101.2.1, N1102.1 . X 2. Identify on the mechanical drawing the required insulation R-value for all HVAC ducts. IRC Section N1103.3 X 3. Identify on the mechanical drawing the required equipment efficiency performance rating. IRC Section N1103.1 X 4. Identify on the mechanical drawing the required insulation for mechanical systems piping. IRC Section N1103.5 X 5. Identify on the mechanical drawing the required HVAC system controls. IRC Section N1103.2 X 6. Identify on the water heater detail, the required water heater efficiency performance rating. IRC Section N1104.1 X 7. Identify on the window and door details/schedules the proposed U-values and solar heat gain coefficients. IRC Section N1102.1, N1102.1.3 X 8. All building joints, seams, penetrations and other sources of air leakage through the building thermal envelope shall be noted to be caulked, weather-stripped, wrapped or otherwise sealed to limit uncontrolled air movement. N1102.1.10 X 9. Recessed lighting fixtures type and rated installation requirements shall be noted on the drawing. Coordinate this with fire-resistive requirements. N1102.1.11 STRUCTURAL FOUNDATION PLAN COMMENTS: X 1. Note and specify soil treatment and other requirements for termite protection. IRC Section R319, R407.1. X 2. Note and specify the finish grades around the building lot indicating requirement for drainage of storm water away from the building foundation. IRC Section R401.3. X 3. Areas that are likely to have expansive, compressible, shifting or other unknown soil characteristics, the building official shall determine whether to require a soil test to determine the soil’s characteristics at a particular location. This test shall be made by an approved agency using an approved method. R401.4 The owner should be aware that certain risks associated with building on unknown foundation soils may be mitigated by obtaining a bona fide soils report by a qualified registrant engineer for the building site. X 4. Foundation plates and sills shall be bolted to the foundation with minimum 1/2 inch bolts at 6 feet or less on center and embedded a minimum 7 inches into the foundation. Note requirements for number of bolts per sill piece and spacing from the ends of end sill piece. Each anchor bolt shall be specified to have a nut and washer. R403.1.6. X 5. Depict and call out on the foundation wall detail that all wood sill plates (interior and exterior, load bearing and non-load bearing) shall be pressure treated or foundation grade redwood. IRC Section R403.1.6 X 6. Structural concrete shall be noted to be consolidated and moist cured in accordance with ACI-318. R402.2 X 7. Note on plans that special inspection is required for anchors in hardened concrete in accordance with IBC Section 1704. STRUCTURAL FRAMING PLAN COMMENTS: X 1. Provide a note on the plans that indicates that prefabricated wood trusses are part of a deferred submittal in accordance with IBC Section 106.3.4.2. X 2. Indicate all braced wall panel locations. Specify the method of bracing and materials to be used. A sealed lateral analysis, prepared by an Arizona Registrant, when the bracing does not comply with the conventional prescriptive provisions. R301.1.3, R602.10.10 X 3. Indicate requirements for positive connection of patio rafters to exterior bearing walls. MECHANICAL PLAN COMMENTS: X 1. Provide a notation on the mechanical drawing that: All ducts shall be sealed substantiately airtight by means of approved and listed tapes (UL 181A, UL-181B) , mastics, gaskets or other approved closure systems. IRC Section M1601.3.1 X 2. Provide combustion air for all liquid and solid fuel-burning appliances including size, type, and location of openings. Combustion air shall not be taken from inside a bedroom (refer to bedroom 2). IRC Chapter 1701 and G2406.2. X 3. The clothes dryer exhaust duct shall be at least the diameter of the appliance outlet and shall terminate on the outside of the building. It shall not exceed 25 feet in length with reductions for bends. The duct shall terminate not less than 3 feet from a property line. IRC Sections M1501 & R302.2. PLUMBING PLAN COMMENTS X 1. Identify the total developed length of gas piping, BTUH gas demand of all appliances and provide suitable gas isometric showing the length of pipes (horizontal and vertical) to each appliance. R106.1.1, G2413; UPC 1217 X 2. Designate the locations of water heaters. Indicate the location of the T and P relief line from the water heater to the exterior of the building. Note the T and P relief line to be full size steel pipe or hard drawn copper tubing extending to the exterior of the building and terminating in a downward position not more than 2 feet or less than 6 inches above grade. The T and P relief line shall not terminate over walkways, patios, carports or other similar areas. Show requirements for emergency drain pan and piping. P2803, P2801; UPC 505.3, UPC 510.7 ELECTRICAL PLAN COMMENTS: X 1. Provide smoke alarms in each sleeping room, outside each sleeping room in the immediate vicinity of the bedrooms and on each additional story of the dwelling, including basements and cellars. IRC Section 313. X 2. In kitchen and dining rooms, a receptacle shall be installed at each wall counter space 12 inches or wider so that no point along the wall is more than 24 inches from a receptacle outlet and shall be GFCI protected. IRC Section E3801.4. X 3. Provide at least one weatherproof receptacle outlet, not more than 6 feet 6 inches above grade and GFCI protected, at the front and back of each dwelling and within garages and basements. IRC Sections E3801.7, E3801.9, E3802. OUTDOOR LIGHTING CODE: X 1. Provide catalog cuts of all outdoor lighting fixtures identifying fixture shielding or non shielding installation conditions and output lumens for each outdoor lighting fixture. X 2. Provide on the drawing appropriate tabular calculations that identify Outdoor Lighting Code site designation, total site area, allowable lumens per Table 5.1, conditions for installation of outdoor lighting fixture type, total lumens allowed at the site, maximum unshielded lumens at the site, and the actual installed lumens at the site for each fixture type. (see illustration attached) Sincerely, BROWN & ASSOCIATES Michael J. Brown, C.B.O. President MB:jah |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/15/2006 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 02/15/2006 | SUE REEVES | REJECT SHELF | Completed |