Permit Number - T06CM00099
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/06/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the natural gas piping design to include the gas-fired water heater. Reference Section 103.2.3, UPC 2003. 2. If the water heater is not provided with integral heat traps, provide pipe insulation (0.5" minimum, with a maximum conductivity of 0.27 BTU/inch-hour-degree Fahrenheit) on the first 8'-0" of the CW and HW pipes. Reference Section 804.5, IECC 2003. |
| 03/07/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the bleed drain for the evaporative cooler to terminate in the suite controlling the evaporative cooler. Reference Section 807.2, UPC 2003 2. Comment not addressed. Provide guards for equipment located within 10 feet of a roof edge or of a walking surface that is elevated more than 30 inches above the adjoining grade. Reference Section 304.10, IMC 2003. 3. Comment not addressed. Show that a separation of at least ten feet exists between air intake openings and exhaust openings. Reference 401.5, IMC 2003. |
| 03/16/2006 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/23/2006 | GBONILL1 | OUT TO CUSTOMER | Completed |
| 03/23/2006 | SUE REEVES | REJECT SHELF | Completed |