Review Date Reviewer's Name Type of Review Description Status Comments
03/06/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the natural gas piping design to include the gas-fired water heater. Reference Section 103.2.3, UPC 2003.
2. If the water heater is not provided with integral heat traps, provide pipe insulation (0.5" minimum, with a maximum conductivity of 0.27 BTU/inch-hour-degree Fahrenheit) on the first 8'-0" of the CW and HW pipes. Reference Section 804.5, IECC 2003.
03/07/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the bleed drain for the evaporative cooler to terminate in the suite controlling the evaporative cooler. Reference Section 807.2, UPC 2003
2. Comment not addressed. Provide guards for equipment located within 10 feet of a roof edge or of a walking surface that is elevated more than 30 inches above the adjoining grade. Reference Section 304.10, IMC 2003.
3. Comment not addressed. Show that a separation of at least ten feet exists between air intake openings and exhaust openings. Reference 401.5, IMC 2003.
03/16/2006 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/23/2006 GBONILL1 OUT TO CUSTOMER Completed
03/23/2006 SUE REEVES REJECT SHELF Completed