Review Date Reviewer's Name Type of Review Description Status Comments
01/19/2006 GERRY KOZIOL WWM REVIEW Denied need to review location of connection to public sewer
02/10/2006 STANTEC 2ND PARTY REVIEW REVIEW Denied February 09, 2006


To: City of Tucson Development Services Department
201 N. Stone Avenue, First Floor
Tucson, Arizona 85701
Attn: David Mann, P.E., Building Code Division

Cc: Gaston Marchand, Architect
12 W. Sahuaro Vista1
Tucson, Arizona

Re: Arreguin Guest House – New Structure
City of Tucson No. T06CM00037
Stantec Project No. 816-30015-01 (076)




Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back-check time, we request that you please provide revised plans and calculations, clouding any changes, along with a written response to each of the noted items indicating the action taken.

SCOPE OF REVIEW:

The scope of this review covers Architectural, Structural, Plumbing, Mechanical, Model Energy and Electrical codes. All code references are to the 2003 International Residential Code (IRC). Applicants may reference the 2003 UPC for plumbing. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL:

The site plan contains out of date Code cycles and Code references, replace referencing the City enforced codes.

ARCHITECTURAL:

There are no comments to address.

STRUCTURAL:

Denote amount of anchors or hold down locations and length of each wall segment per each braced wall. [2003 IRC Sec. R602.10]. Bracing needs to follow the following criteria and be denoted on the framing plan, floor plan and/or foundation plan:

Type of Brace - Methods 1, 2, 3, 4, 5, 6, 7 or 8, depict calculation of wall lengths required per method chosen. [2003 IRC Sec. R602.10.3].

Amount of Bracing - Located at each end and at least every 25 feet on center but not less than 16% of braced wall line for Method 3 and 25% of braced wall line for methods 2, 4, 5, 6, 7 or 8. [2003 IRC Sec. R602.10 & R602.10.1].

The general framing as depicted does not recognize the lateral resisting principals per [IRC Sec’s R602.10.2.3 and Sec’s R602.10.4 through R602.10.10]. Corrections required to type of braced wall used per each location depicted.

The height of the CMU wall detail requires it have design substantiation. The detail 9/4 does not denote the use of bond beams as required from the Pima County City of Tucson Standard Details.

The framing plan does not depict the location, wood bearing area required or use of bearing posts and their connections at the denoted headers and girder truss from the roof framing plan submitted. Denote all on plan.

Provide manufacturer’s calculations and data for pre-fabricated trusses upon next submittal. Truss calculations must be signed, dated and wet-sealed by an engineer who is registered in Arizona. Truss calculations shall be cross-referenced to the framing plan. The City of Tucson will allow a deferred submittal on trusses with an approved request letter signed by the building official.

PLUMBING PLANS:

The tub has no plumbing waste connection. Provide.

‘Water Heater Schematic’, sheet 6, the backcheck valve is missing from the cold water. The expansion tank is missing from the diagram.

MECHANICAL PLANS:

The amount of duct clearance required within the prefab wood truss webs needs to be verified upon the next submittal.

Show exhaust fan locations for bathrooms, water closet compartments, separated baths and laundry rooms in lieu of operable windows [2003 IRC Sec. R303.3].

ELECTRICAL PLANS:

When a new residence such as this project is added, the entire site must be brought into lighting code compliance. Therefore a plan depicting all site light usage must be submitted. Outdoor lighting Code 5.1.1, 5.1.2 & Section 4 of the code notes that fixture types installed under canopies or roof must be full cut of fixture types themselves, not denoted as such by arbitrary placement. Photo(s) of existing use for proof of fixture(s) are accepted in lieu of manufacturer’s cut sheets.

The City of Tucson submittal package shall include two (2) – copies of all exterior light fixtures compliant to the Outdoor Lighting Code for the location area within Pima County the addition is to be built.

Denote on the plan that all outlets serving the kitchen counters shall be GFI protected per 2003 IRC Section E3802.6..

MODEL ENERGY CODE:

Provide Energy Calculations [2000 IECC], or note compliance with the default minimums [2003 IRC Table 1102.1]. Reference the values of the table.


-End of Review-


If you have any questions, please call (520) 750-7474.


Sincerely,
Stantec Consulting Inc.




Steven L. Nygren, R.A.
Senior Plans Examiner

SLN:sln