Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06CM00023
Parcel: 13316013B

Address:
6500 E GRANT RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM00023
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2006 JIM EGAN FIRE REVIEW Approved
01/05/2006 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Denied 1.Provide the size,type,insulation etc. of the existing service lateral conductors as well as main breaker ratings and quantities.
01/17/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show that the condensing units have stop valves as required by Section 1107.7, IMC 2003.
01/17/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The applicable code for all commercial plumbing projects is the 2003 Uniform Plumbing Code with Local Amendments.
2. The trap size for an indirect waste receptor is to be based on the total drainage capacity of the fixtures draining into the receptor (Reference Table 7-3, footnote 1, UPC 2003). A 3" trap, as shown for FD-1, is rated for 6 fixture units which will require the vent serving over 4 receptors to be resized per Table 7-5, UPC 2003.
3. Revise the locations of the indirect waste receptors as required to insure that they are readily accessible for inspection and cleaning. Reference Section 804.1, UPC 2003.
01/17/2006 ROBERT SHERRY WATER REVIEW Approved
01/19/2006 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
01/26/2006 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/16/2006 SUE REEVES OUT TO CUSTOMER Completed
02/16/2006 SUE REEVES REJECT SHELF Completed