Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM00023
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/05/2006 | JIM EGAN | FIRE | REVIEW | Approved | |
| 01/05/2006 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1.Provide the size,type,insulation etc. of the existing service lateral conductors as well as main breaker ratings and quantities. |
| 01/17/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show that the condensing units have stop valves as required by Section 1107.7, IMC 2003. |
| 01/17/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The applicable code for all commercial plumbing projects is the 2003 Uniform Plumbing Code with Local Amendments. 2. The trap size for an indirect waste receptor is to be based on the total drainage capacity of the fixtures draining into the receptor (Reference Table 7-3, footnote 1, UPC 2003). A 3" trap, as shown for FD-1, is rated for 6 fixture units which will require the vent serving over 4 receptors to be resized per Table 7-5, UPC 2003. 3. Revise the locations of the indirect waste receptors as required to insure that they are readily accessible for inspection and cleaning. Reference Section 804.1, UPC 2003. |
| 01/17/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 01/19/2006 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 01/26/2006 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/16/2006 | SUE REEVES | OUT TO CUSTOMER | Completed |
| 02/16/2006 | SUE REEVES | REJECT SHELF | Completed |