Permit Number: T06CM00022
Parcel: Unknown

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM00022
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/23/2006 GERRY KOZIOL WWM REVIEW Approved
03/20/2006 MARTIN BROWN FIRE REVIEW Denied 1) Additional fire hydrant required per COT amendment to the IFC, 2003, Section 508.5.1
2) Hanger must be specified on plan as "Group III Hanger, per requirements of NFPA 409
3) Fire Department requests letter from owner stating Hanger will not be used for any purpose outside the parameters established by NFPA 409 for Group III hangers

Final Status

Task End Date Reviewer's Name Type of Review Description
03/29/2006 ADRIANNE OLIVO OUT TO CUSTOMER Completed
03/29/2006 SUE REEVES REJECT SHELF Completed