Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T06CM00022
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/23/2006 | GERRY KOZIOL | WWM | REVIEW | Approved | |
03/20/2006 | MARTIN BROWN | FIRE | REVIEW | Denied | 1) Additional fire hydrant required per COT amendment to the IFC, 2003, Section 508.5.1 2) Hanger must be specified on plan as "Group III Hanger, per requirements of NFPA 409 3) Fire Department requests letter from owner stating Hanger will not be used for any purpose outside the parameters established by NFPA 409 for Group III hangers |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
03/29/2006 | ADRIANNE OLIVO | OUT TO CUSTOMER | Completed |
03/29/2006 | SUE REEVES | REJECT SHELF | Completed |